32 KiB
APC UPS Galaxy 3500 by SNMP
Overview
The template to monitor APC UPS Galaxy 3500 by Zabbix SNMP agent. Note: please, use the latest version of the firmware for your NMC in order for the template to work correctly.
Requirements
Zabbix version: 7.0 and higher.
Tested versions
This template has been tested on:
- APC UPS Galaxy 3500
Configuration
Zabbix should be configured according to the instructions in the Templates out of the box section.
Setup
1. Create a host for APC UPS Galaxy 3500 management IP as SNMPv2 interface.
2. Link the template to the host.
3. Customize macro values if needed.
Macros used
Name | Description | Default |
---|---|---|
{$BATTERY.TEMP.MAX.WARN} | Maximum battery temperature for trigger expression. |
55 |
{$BATTERY.CAPACITY.MIN.WARN} | Minimum battery capacity percentage for trigger expression. |
50 |
{$UPS.OUTPUT.MAX.WARN} | Maximum output load in % for trigger expression. |
80 |
{$UPS.INPUT_FREQ.MIN.WARN} | Minimum input frequency for trigger expression. |
49.7 |
{$UPS.INPUT_FREQ.MAX.WARN} | Maximum input frequency for trigger expression. |
50.3 |
{$UPS.INPUT_VOLT.MIN.WARN} | Minimum input voltage for trigger expression. |
197 |
{$UPS.INPUT_VOLT.MAX.WARN} | Maximum input voltage for trigger expression. |
243 |
{$TIME.PERIOD} | Time period for trigger expression. |
15m |
{$SNMP.TIMEOUT} | The time interval for SNMP agent availability trigger expression. |
5m |
Items
Name | Description | Type | Key and additional info |
---|---|---|---|
APC UPS Galaxy 3500: Model | MIB: PowerNet-MIB The UPS model name (e.g. 'APC Smart-UPS 600'). |
SNMP agent | system.model[upsBasicIdentModel] Preprocessing
|
APC UPS Galaxy 3500: Serial number | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. |
SNMP agent | system.sn[upsAdvIdentSerialNumber] Preprocessing
|
APC UPS Galaxy 3500: Battery status | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. |
SNMP agent | battery.status[upsBasicBatteryStatus] Preprocessing
|
APC UPS Galaxy 3500: Battery capacity | MIB: PowerNet-MIB The remaining battery capacity expressed as percentage of full capacity. |
SNMP agent | battery.capacity[upsHighPrecBatteryCapacity] Preprocessing
|
APC UPS Galaxy 3500: Battery runtime remaining | MIB: PowerNet-MIB The UPS battery run time remaining before battery exhaustion. |
SNMP agent | battery.runtime_remaining[upsAdvBatteryRunTimeRemaining] Preprocessing
|
APC UPS Galaxy 3500: Battery voltage | MIB: PowerNet-MIB The actual battery bus voltage in Volts. |
SNMP agent | battery.voltage[upsHighPrecBatteryActualVoltage] Preprocessing
|
APC UPS Galaxy 3500: Battery last replace date | MIB: PowerNet-MIB The date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set at the factory. When the UPS batteries are replaced, this value should be reset by the administrator. For Symmetra PX 250/500 this OID is read-only and is configurable in the local display only. |
SNMP agent | battery.last_replace_date[upsBasicBatteryLastReplaceDate] Preprocessing
|
APC UPS Galaxy 3500: Battery replace indicator | MIB: PowerNet-MIB Indicates whether the UPS batteries need replacement. |
SNMP agent | battery.replace_indicator[upsAdvBatteryReplaceIndicator] Preprocessing
|
APC UPS Galaxy 3500: External battery packs count | MIB: PowerNet-MIB The number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. |
SNMP agent | battery.external_packs_count[upsAdvBatteryNumOfBattPacks] Preprocessing
|
APC UPS Galaxy 3500: Battery temperature | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. |
SNMP agent | battery.temperature[upsHighPrecBatteryTemperature] Preprocessing
|
APC UPS Galaxy 3500: Input voltage | MIB: PowerNet-MIB The current utility line voltage in VAC. |
SNMP agent | input.voltage[upsHighPrecInputLineVoltage] Preprocessing
|
APC UPS Galaxy 3500: Input frequency | MIB: PowerNet-MIB The current input frequency to the UPS system in Hz. |
SNMP agent | input.frequency[upsHighPrecInputFrequency] Preprocessing
|
APC UPS Galaxy 3500: Input fail cause | MIB: PowerNet-MIB The reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) -- if there is no transfer yet. - highLineVoltage(2) -- if the transfer to battery is caused by an over voltage greater than the high transfer voltage. - brownout(3) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - blackout(4) -- if the duration of the outage is greater than five seconds and the line voltage is between 40% of the rated output voltage and ground. - smallMomentarySag(5) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and the low transfer voltage. - deepMomentarySag(6) -- if the duration of the outage is less than five seconds and the line voltage is between 40% of the rated output voltage and ground. The variable is set to - smallMomentarySpike(7) -- if the line failure is caused by a rate of change of input voltage less than ten volts per cycle. - largeMomentarySpike(8) -- if the line failure is caused by a rate of change of input voltage greater than ten volts per cycle. - selfTest(9) -- if the UPS was commanded to do a self test. - rateOfVoltageChange(10) -- if the failure is due to the rate of change of the line voltage. |
SNMP agent | input.fail[upsAdvInputLineFailCause] Preprocessing
|
APC UPS Galaxy 3500: Output voltage | MIB: PowerNet-MIB The output voltage of the UPS system in VAC. |
SNMP agent | output.voltage[upsHighPrecOutputVoltage] Preprocessing
|
APC UPS Galaxy 3500: Output load | MIB: PowerNet-MIB The current UPS load expressed as percentage of rated capacity. |
SNMP agent | output.load[upsHighPrecOutputLoad] Preprocessing
|
APC UPS Galaxy 3500: Output current | MIB: PowerNet-MIB The current in amperes drawn by the load on the UPS. |
SNMP agent | output.current[upsHighPrecOutputCurrent] Preprocessing
|
APC UPS Galaxy 3500: Output status | MIB: PowerNet-MIB The current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1). During self-test most UPSes report onBattery(3) but some that support it will report onBatteryTest(15). To determine self-test status across all UPSes, refer to the upsBasicStateOutputState OID. |
SNMP agent | output.status[upsBasicOutputStatus] Preprocessing
|
APC UPS Galaxy 3500: Uptime (network) | MIB: SNMPv2-MIB The time (in hundredths of a second) since the network management portion of the system was last re-initialized. |
SNMP agent | system.net.uptime[sysUpTime.0] Preprocessing
|
APC UPS Galaxy 3500: Uptime (hardware) | MIB: HOST-RESOURCES-MIB The amount of time since this host was last initialized. Note that this is different from sysUpTime in the SNMPv2-MIB [RFC1907] because sysUpTime is the uptime of the network management portion of the system. |
SNMP agent | system.hw.uptime[hrSystemUptime.0] Preprocessing
|
APC UPS Galaxy 3500: SNMP traps (fallback) | The item is used to collect all SNMP traps unmatched by other snmptrap items |
SNMP trap | snmptrap.fallback |
APC UPS Galaxy 3500: System location | MIB: SNMPv2-MIB The physical location of this node (e.g., `telephone closet, 3rd floor'). If the location is unknown, the value is the zero-length string. |
SNMP agent | system.location[sysLocation.0] Preprocessing
|
APC UPS Galaxy 3500: System contact details | MIB: SNMPv2-MIB The textual identification of the contact person for this managed node, together with information on how to contact this person. If no contact information is known, the value is the zero-length string. |
SNMP agent | system.contact[sysContact.0] Preprocessing
|
APC UPS Galaxy 3500: System object ID | MIB: SNMPv2-MIB The vendor's authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining |
SNMP agent | system.objectid[sysObjectID.0] Preprocessing
|
APC UPS Galaxy 3500: System name | MIB: SNMPv2-MIB An administratively-assigned name for this managed node.By convention, this is the node's fully-qualified domain name. If the name is unknown, the value is the zero-length string. |
SNMP agent | system.name[sysName.0] Preprocessing
|
APC UPS Galaxy 3500: System description | MIB: SNMPv2-MIB A textual description of the entity. This value should include the full name and version identification of the system's hardware type, software operating-system, and networking software. |
SNMP agent | system.descr[sysDescr.0] Preprocessing
|
APC UPS Galaxy 3500: SNMP agent availability | Availability of SNMP checks on the host. The value of this item corresponds to availability icons in the host list. Possible value: 0 - not available 1 - available 2 - unknown |
Zabbix internal | zabbix[host,snmp,available] Preprocessing
|
Triggers
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
APC UPS Galaxy 3500: Battery has an internal error condition | A battery installed has an internal error condition. |
last(/APC UPS Galaxy 3500 by SNMP/battery.status[upsBasicBatteryStatus])=4 |
Average | |
APC UPS Galaxy 3500: Battery is Low | The UPS will be unable to sustain the current load, and its services will be lost if power is not restored. |
last(/APC UPS Galaxy 3500 by SNMP/battery.status[upsBasicBatteryStatus])=3 |
Average | |
APC UPS Galaxy 3500: Battery has low capacity | last(/APC UPS Galaxy 3500 by SNMP/battery.capacity[upsHighPrecBatteryCapacity]) < {$BATTERY.CAPACITY.MIN.WARN} |
High | ||
APC UPS Galaxy 3500: Battery needs replacement | A battery installed has an internal error condition. |
last(/APC UPS Galaxy 3500 by SNMP/battery.replace_indicator[upsAdvBatteryReplaceIndicator])=2 |
High | |
APC UPS Galaxy 3500: Battery has high temperature | min(/APC UPS Galaxy 3500 by SNMP/battery.temperature[upsHighPrecBatteryTemperature],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} |
High | ||
APC UPS Galaxy 3500: Unacceptable input voltage | min(/APC UPS Galaxy 3500 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/input.voltage[upsHighPrecInputLineVoltage],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN}) |
High | ||
APC UPS Galaxy 3500: Unacceptable input frequency | min(/APC UPS Galaxy 3500 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > 0 and (min(/APC UPS Galaxy 3500 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) > {$UPS.INPUT_FREQ.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/input.frequency[upsHighPrecInputFrequency],{$TIME.PERIOD}) < {$UPS.INPUT_FREQ.MIN.WARN}) |
High | ||
APC UPS Galaxy 3500: Output load is high | A battery installed has an internal error condition. |
min(/APC UPS Galaxy 3500 by SNMP/output.load[upsHighPrecOutputLoad],{$TIME.PERIOD}) > {$UPS.OUTPUT.MAX.WARN} |
High | |
APC UPS Galaxy 3500: UPS is Timed Sleeping | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=5 |
Average | ||
APC UPS Galaxy 3500: UPS is Switched Bypass | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=9 |
Average | ||
APC UPS Galaxy 3500: UPS is Software Bypass | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=6 |
Average | ||
APC UPS Galaxy 3500: UPS is Sleeping Until Power Return | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=11 |
Average | ||
APC UPS Galaxy 3500: UPS is Rebooting | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=8 |
Average | ||
APC UPS Galaxy 3500: UPS is On Smart Trim | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=12 |
Average | ||
APC UPS Galaxy 3500: UPS is on Smart Boost | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=4 |
Average | ||
APC UPS Galaxy 3500: UPS is on battery | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=3 |
Average | ||
APC UPS Galaxy 3500: UPS is Off | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=7 |
Average | ||
APC UPS Galaxy 3500: UPS is Emergency Static Bypass | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=16 |
Average | ||
APC UPS Galaxy 3500: UPS is Hardware Failure Bypass | last(/APC UPS Galaxy 3500 by SNMP/output.status[upsBasicOutputStatus])=10 |
Average | ||
APC UPS Galaxy 3500: Host has been restarted | Uptime is less than 10 minutes. |
(last(/APC UPS Galaxy 3500 by SNMP/system.hw.uptime[hrSystemUptime.0])>0 and last(/APC UPS Galaxy 3500 by SNMP/system.hw.uptime[hrSystemUptime.0])<10m) or (last(/APC UPS Galaxy 3500 by SNMP/system.hw.uptime[hrSystemUptime.0])=0 and last(/APC UPS Galaxy 3500 by SNMP/system.net.uptime[sysUpTime.0])<10m) |
Warning | Manual close: Yes Depends on:
|
APC UPS Galaxy 3500: System name has changed | The name of the system has changed. Acknowledge to close the problem manually. |
last(/APC UPS Galaxy 3500 by SNMP/system.name[sysName.0],#1)<>last(/APC UPS Galaxy 3500 by SNMP/system.name[sysName.0],#2) and length(last(/APC UPS Galaxy 3500 by SNMP/system.name[sysName.0]))>0 |
Info | Manual close: Yes |
APC UPS Galaxy 3500: No SNMP data collection | SNMP is not available for polling. Please check device connectivity and SNMP settings. |
max(/APC UPS Galaxy 3500 by SNMP/zabbix[host,snmp,available],{$SNMP.TIMEOUT})=0 |
Warning |
LLD rule Input phases discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
Input phases discovery | The input phase identifier. OID upsPhaseInputPhaseIndex.1.1 |
SNMP agent | input.phases.discovery |
Item prototypes for Input phases discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
{#PHASEINDEX}: Phase input voltage | MIB: PowerNet-MIB The input voltage in VAC, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}] Preprocessing
|
{#PHASEINDEX}: Phase input current | MIB: PowerNet-MIB The input current in 0.1 amperes, or -0.1 if it's unsupported by this UPS. |
SNMP agent | phase.input.current[upsPhaseInputCurrent.1.1.{#PHASEINDEX}] Preprocessing
|
Trigger prototypes for Input phases discovery
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} input voltage | min(/APC UPS Galaxy 3500 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/phase.input.voltage[upsPhaseInputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} |
High |
LLD rule Output phases discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
Output phases discovery | The output phase identifier. OID upsPhaseOutputPhaseIndex.1.1 |
SNMP agent | output.phases.discovery |
Item prototypes for Output phases discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
{#PHASEINDEX}: Phase output voltage | MIB: PowerNet-MIB The output voltage in VAC, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}] Preprocessing
|
{#PHASEINDEX}: Phase output current | MIB: PowerNet-MIB The output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.output.current[upsPhaseOutputCurrent.1.1.{#PHASEINDEX}] Preprocessing
|
{#PHASEINDEX}: Phase output load, % | MIB: PowerNet-MIB The percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS. |
SNMP agent | phase.output.load.percent[upsPhaseOutputPercentLoad.1.1.{#PHASEINDEX}] Preprocessing
|
Trigger prototypes for Output phases discovery
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
{#PHASEINDEX}: Unacceptable phase {#PHASEINDEX} output voltage | min(/APC UPS Galaxy 3500 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) > {$UPS.INPUT_VOLT.MAX.WARN} or max(/APC UPS Galaxy 3500 by SNMP/phase.output.voltage[upsPhaseOutputVoltage.1.1.{#PHASEINDEX}],{$TIME.PERIOD}) < {$UPS.INPUT_VOLT.MIN.WARN} |
High |
LLD rule External battery packs discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
External battery packs discovery | SNMP agent | battery.packs.discovery |
Item prototypes for External battery packs discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status | MIB: PowerNet-MIB The status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is not restored. The amount of run time in reserve at the time of low battery can be configured by the upsAdvConfigLowBatteryRunTime. A batteryInFaultCondition(4)value indicates that a battery installed has an internal error condition. |
SNMP agent | battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery temperature | MIB: PowerNet-MIB The current internal UPS temperature in Celsius. Temperatures below zero read as 0. |
SNMP agent | battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Serial number | MIB: PowerNet-MIB An 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspond to the serial number on the rear of the UPS. |
SNMP agent | system.sn[upsHighPrecBatteryPackSerialNumber.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery estimated replace date | MIB: PowerNet-MIB The battery cartridge estimated battery replace date. |
SNMP agent | battery.estimated_replace_date[upsHighPrecBatteryPackCartridgeReplaceDate.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery pack cartridge health | MIB: PowerNet-MIB The battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace battery bit 3 Battery lifetime near end acknowledged, order replacement cartridge bit 4 Battery lifetime exceeded acknowledged, replace battery bit 5 Battery measured lifetime near end, order replacement cartridge bit 6 Battery measured lifetime near end acknowledged, order replacement cartridge |
SNMP agent | battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}] Preprocessing
|
Trigger prototypes for External battery packs discovery
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery status is not okay | The battery cartridge status: |
find(/APC UPS Galaxy 3500 by SNMP/battery.pack.status[upsHighPrecBatteryPackCartridgeStatus.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0{16})$")=0 |
Warning | |
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery has high temperature | min(/APC UPS Galaxy 3500 by SNMP/battery.temperature[upsHighPrecBatteryPackTemperature.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],{$TIME.PERIOD}) > {$BATTERY.TEMP.MAX.WARN} |
High | ||
{#BATTERY_PACK}.{#CARTRIDGE_INDEX}: Battery lifetime is not okay | The battery cartridge health. |
find(/APC UPS Galaxy 3500 by SNMP/battery.pack.cartridge_health[upsHighPrecBatteryPackCartridgeHealth.{#BATTERY_PACK}.{#CARTRIDGE_INDEX}],,"regexp","^(0)[0|1]{15}$")=1 |
Warning |
LLD rule External bad battery packs discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
External bad battery packs discovery | Discovery of the number of external defective battery packs. |
SNMP agent | battery.packs.bad.discovery |
Item prototypes for External bad battery packs discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
{#SNMPINDEX}: External battery packs bad | MIB: PowerNet-MIB The number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME. |
SNMP agent | battery.external_packs_bad[upsAdvBatteryNumOfBadBattPacks.{#SNMPINDEX}] Preprocessing
|
LLD rule External sensor port 1 discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
External sensor port 1 discovery | uioSensorStatusTable |
SNMP agent | external.sensor1.discovery |
Item prototypes for External sensor port 1 discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
{#EXTERNAL_SENSOR1_NAME}: Temperature sensor | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. |
SNMP agent | external.sensor.temperature[uioSensorStatusTemperatureDegC.1.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR1_NAME}: Humidity sensor | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. |
SNMP agent | external.sensor.humidity[uioSensorStatusHumidity.1.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR1_NAME}: Sensor alarm status | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) |
SNMP agent | external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}] Preprocessing
|
Trigger prototypes for External sensor port 1 discovery
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Not Applicable | The external sensor does not work or is not connected. |
last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=4 |
Info | |
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Warning | The external sensor has returned a value greater than the warning threshold. |
last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=2 |
Average | |
{#EXTERNAL_SENSOR1_NAME}: Sensor has status Critical | The external sensor has returned a value greater than the critical threshold. |
last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.1.{#SNMPINDEX}])=3 |
High |
LLD rule External sensor port 2 discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
External sensor port 2 discovery | uioSensorStatusTable |
SNMP agent | external.sensor2.discovery |
Item prototypes for External sensor port 2 discovery
Name | Description | Type | Key and additional info |
---|---|---|---|
{#EXTERNAL_SENSOR2_NAME}: Temperature sensor | MIB: PowerNet-MIB The sensor's current temperature reading in Celsius. -1 indicates an invalid reading due to lost communications. |
SNMP agent | external.sensor.temperature[uioSensorStatusTemperatureDegC.2.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR2_NAME}: Humidity sensor | MIB: PowerNet-MIB The sensor's current humidity reading - a relative humidity percentage. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost communications. |
SNMP agent | external.sensor.humidity[uioSensorStatusHumidity.2.{#SNMPINDEX}] Preprocessing
|
{#EXTERNAL_SENSOR2_NAME}: Sensor alarm status | MIB: PowerNet-MIB The alarm status of the sensor. Possible values: uioNormal (1), uioWarning (2), uioCritical (3), sensorStatusNotApplicable (4) |
SNMP agent | external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}] Preprocessing
|
Trigger prototypes for External sensor port 2 discovery
Name | Description | Expression | Severity | Dependencies and additional info |
---|---|---|---|---|
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Not Applicable | The external sensor does not work or is not connected. |
last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=4 |
Info | |
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Warning | The external sensor has returned a value greater than the warning threshold. |
last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=2 |
Average | |
{#EXTERNAL_SENSOR2_NAME}: Sensor has status Critical | The external sensor has returned a value greater than the critical threshold. |
last(/APC UPS Galaxy 3500 by SNMP/external.sensor.status[uioSensorStatusAlarmStatus.2.{#SNMPINDEX}])=3 |
High |
Feedback
Please report any issues with the template at https://support.zabbix.com
You can also provide feedback, discuss the template, or ask for help at ZABBIX forums